Service Code: 06

Load Testing & Performance Check

Verifying true real-world power capacity and transient load response.

Load Testing & Performance Check

Infocus Power Care • Technical Field Execution

Load Testing & Performance Check

Service Overview

Protecting Your Generator Performance

Performance checks and load testing help verify that the DG set responds correctly under operating conditions.

A generator running on light or no-load during routine weekly tests does not prove it will sustain full facility loads during a major blackout. In fact, prolonged light-load operation causes engine wet-stacking and carbon buildup. Our controlled load testing validates your generator's actual thermal, mechanical, and electrical capacity.

What This Service Involves

Systematic procedural tasks performed by our certified engineering team.

Resistive load bank testing across stepped loads (25%, 50%, 75%, 100%, and 110% peak)
Transient response analysis during sudden step-load applications
Cooling system thermal equilibrium measurement under sustained maximum load
Alternator voltage regulation (AVR) and frequency governor stability tracking
Exhaust temperature, boost pressure, and backpressure evaluation
Wet-stacking carbon burnout and internal engine de-coking through controlled loading
Comprehensive digital performance graphing and certification documentation

Key Benefits for Your Facility

Measurable advantages in reliability, cost efficiency, and asset longevity.

1

Proves beyond doubt that the generator will perform reliably during actual power outages

2

Cleanses unburnt fuel and carbon deposits from the turbocharger and exhaust system

3

Validates cooling and fuel systems under maximum real-world thermal stress

4

Detects weak batteries, slipping belts, or failing injectors under heavy draw

5

Provides verifiable data for regulatory audits, insurance, and facility compliance

Primary Engineering Checkpoints

Standard Quality Protocol
Voltage Drop & Recovery Time
Frequency Dip & Steady-State Regulation
Cooling Water & Lube Oil Maximum Temperature
Exhaust Smoke Color & Density
Alternator Stator & Rotor Temperature Rise
Direct Service Request

Need Load Testing?

Connect with our technical desk for scheduling or custom quotes.

24x7 Emergency Line: +91 79948 35150

100% Genuine OEM Spares & Filters

Kerala-Wide Rapid Technical Response

LET'S KEEP YOUR POWER READY

Whether you require routine service, AMC support, genuine spares, installation assistance, breakdown response, or performance checking, Infocus Power Care is ready to support your DG set requirements.

100% Genuine OEM Spares
24×7 Emergency Support
Cochin & Trivandrum Hubs